Model |
TP901II |
TP902II |
TP903 II |
TP906II |
TP9010 II | |
Capacity |
1KVA |
2KVA |
3KVA |
6KVA |
10KVA | |
INPUT | ||||||
Rated input voltage |
220V | |||||
Rated input frequency |
50Hz/60Hz (self-adaption ) | |||||
Input voltage Range |
110~300 VAC (Half load),140~300VAC (Full load) | |||||
Input frequency Range |
45-55Hz +/-0.5% 50Hz | |||||
55-65Hz +/-0.5% 60Hz | ||||||
Phase |
single phase+N+GND | |||||
Power factor |
=0.98 |
=0.99 | ||||
Input current (liner full load) |
4.0A |
8.1A |
12.1A |
24.2A |
40.4A | |
THD |
?5% | |||||
ByPass voltage range |
186VAC-252VAC | |||||
OUTPUT | ||||||
Rated voltage |
208VAC/220VAC/230VAC/240VAC can be set on LCD | |||||
Power factor |
0.8 | |||||
Voltage distortion |
±2% | |||||
DC component voltage |
=200mv | |||||
Output current crest factor |
3:1 | |||||
Rated frequency | ||||||
AC mode |
same as input frequency | |||||
Battery mode |
50/60±0.2Hz | |||||
Phase lock speed |
=1Hz/s | |||||
Wave distortion |
100% linear load <3%;100%; nonlinear load <5% | |||||
Transfer time | ||||||
From Mains mode to battery mode |
0ms | |||||
From battery mode to Mains mode |
0ms | |||||
From Mains mode to bypass mode |
<4ms | |||||
From bypass mode to Mains mode |
<4ms | |||||
From normal mode to ECO mode |
=10ms | |||||
System Efficiency |
Full load |
?90 % |
?92% | |||
ECO mode |
?94% | |||||
Inverter overload capacity |
105%~150% 30s transfer to bypass mode giving alarm;
>150% 300ms transfer to bypass mode giving alarm; | |||||
Battery | ||||||
Battery type |
Lead Acid maintenance free battery | |||||
DC voltage |
24V DC |
48V DC |
72V DC |
168V DC |
168V DC | |
Inbuilt battery |
7AH/12V |
7AH/12V |
7AH/12V |
9AH/12V |
9AH/12V | |
Battery quantity |
2 |
4 |
6 |
14 |
14 | |
Charge | ||||||
Output voltage |
27.5±0.4V |
55±0.6V |
82.5±0.9V |
193.7±0.9V |
193.7±0.9V | |
Charge method |
Three-stage charging | |||||
Recharge time |
90% capacity after 5hrs charging (standard model) | |||||
According to battery capacity(long time model) | ||||||
Input voltage range |
80VAC~300VAC | |||||
Charge current |
Standard model:1A | |||||
Long time model: 6A
(can extend to 12A) | ||||||
Protection | ||||||
Over-temp protection
Fan testing protection
AC L and N connect wrong protection
Output short circuit protection | ||||||
Control | ||||||
Silence; cold start; AC restart; Auto restart. | ||||||
Communication | ||||||
RS232, SNMP card , USB | ||||||
Software function
Statue analyze: Switch on/off UPS system, Monitor UPS working state ,store history | ||||||
Display |
LCD/LED | |||||
System Operating Environment | ||||||
Operating environment |
Operation tem. |
0 ~ 40 ? | ||||
Store tem. |
-25? ~ 55 ? | |||||
Humidity |
20 ~ 90%(non-condensing) | |||||
Altitude |
0m used with power derated | |||||
Noise |
<50db (1-3kva) | |||||
<55db(6-10kva) | ||||||
Dimension(W*D*H) |
357*144*215 |
439*190*341 |
439*190*341 |
514*262*455
(Long time model) | ||
574*262*710
(Standard model) | ||||||
Weight(Kg) |
Long time model |
6 |
12 |
12.5 |
42 | |
Standard model |
10 |
20 |
24 |
57 |